Blitz Fire-Rated Containment
Blitz Systems Blitz Fire-Rated Containment: nine tested systems of BT3 and BT5 cable tray, BM50 mesh and Nema 2, 3 and 4 fire-rated ladder, in widths from 150 to 600 mm. The data sheet states testing to AS/NZS3013:2005 Appendix C Classification WS5X (2 hours). Returns the tray, mesh or ladder code, kit code, rod centres, tested load, support span, rod diameter, length and stacking, with a check of the cable load against the tested load. Values are as printed on the manufacturer's data sheet.
This listing is not verified by the manufacturer. It is the user's responsibility to review the product brochures and technical notes related to the information presented in this listing and ensure alignment with these resources. If you identify any inconsistencies, errors, or intellectual property issues, please email us at [email protected].
Calculated Values
Tray, mesh or ladder code
Code = 0
Kit code
Kit = 0
Rod centres
cr = 0
Tested load
wt = 1 kg/m
Support span
s = 1 m
Threaded rod diameter
dr = 1 mm
Length, as printed
L = 0
Stacking, as printed
Tier = 0
Cable load check against the tested load
Check = 0
Tested systems from the Blitz Systems Blitz Fire-Rated Containment data sheet, as printed. Select the tested system, then the containment, width and tested arrangement listed for it. The listing returns the codes, the tested load, the support span, the threaded rod diameter and the rod centres printed for that configuration. Enter the cable load to compare it with the tested load.
The data sheet states: Blitz Fire-Rated containment has been engineered, independently tested and certified to AS/NZS3013:2005 Appendix C Classification WS5X (2 hours) by a NATA accredited facility. Only the configurations printed on the data sheet are offered.
Not Available
The table is not uploaded or the values for the variables: do not match table records.
The table is not uploaded or the values for the variables: do not match table records.
The table is not uploaded or the values for the variables: do not match table records.
Basis and limits
- Source: Blitz Systems Blitz Fire-Rated Containment data sheet (11 pages, no version shown). All values, codes and descriptions are as printed on that sheet.
- Testing, as stated on the data sheet: Blitz Fire-Rated containment has been engineered, independently tested and certified to AS/NZS3013:2005 Appendix C Classification WS5X (2 hours) by a NATA accredited facility. The data sheet gives no test report number, date or laboratory.
- The statement applies to the configurations printed on the data sheet. This listing offers those configurations only and makes no claim for any other containment, width, load, support span, threaded rod, tier arrangement or mounting.
- The tested load is printed per tier where the Load Performance table says so. The cable load entered is compared with that single printed value. No utilisation is shown and no margin is implied.
- The support span is the span printed with the tested load. It is not an input, and no value is interpolated or extrapolated. BT25FR is printed with two combinations of load and support span, and only those two are offered.
- BT5 tray appears on this data sheet only. No BT5 data sheet has been supplied, so no weight, dimension or load data other than the values shown here is available.
- Descriptions that look inconsistent are published as printed and are under query with the manufacturer: the 150FR Support Kit for BT50FR-BT3150 and the 150mm x 6mtr descriptions of all BLVFR and BLHFR kits.
- Ladder length is printed as 3m / 6m, and 3.0m / 6.0m for BLVFR and BLHFR. The data sheet lists 6mtr ladder codes only.
- For BLVFR and BLHFR the data sheet does not state the stacking or the rod centres and does not define the support span.
- The data sheet gives no weights for the fire-rated ladders or the support kits and does not list the contents of the kits beyond the descriptions shown.
- Values from other Blitz Systems data sheets are not combined with these. Threaded rod, anchors, fixings to the structure, the supporting structure, the cables and any fire stopping are not checked.
- Preliminary selection only. Confirm the final design and the scope of the fire test evidence with Blitz Systems.